16
oph
/
ALAR
M
/
Set limit value of the operating hours has been exceeded.
opc
11
/
ALAR
M
/
Set limit of the maximum permissible switching cycles of one
or several stages has been exceeded.
Error code and stage number are flashing alternatingly.
Only the smallest affected stage number is displayed.
opc
11
/
ALAR
M
/
Set limit of the maximum permissible operating hours of one
or several stages has been exceeded.
Error code and stage number are flashing alternatingly.
Only the smallest affected stage number is displayed.
DI
/
ALAR
M
/
The digital-input-alarm provides to record external alarm
signals in the form of a digital signal.
SYS
004F
/
ALAR
M
/
System-Alarm: The message “SYS” appears alternating with a
four-digit failure code on the display. The device is defective
and has to be send back.
If several alarms are active, the alarm messages are exchanged cyclically.
Example: U and I-LOW-alarm are active, the alarm messages are displayed as follows: 3 times error
code
“
U
”, then 3 times “
I
”, then again 3 times starting with “
U
” etc.
In addition to the alarm messages, the following error and status messages are displayed.
Error messages:
Ai
/
abrt
The automatic initialisation (AI) was cancelled due to an error.
The control is set inactive.
An active error message can be reset by pressing the
(ESC) key for 3 s.
Status messages:
fan
Temperature limit 1 has been exceeded; switching output fan is
switched on.
NOTE:
The activation of the switching output fan and the
display of the fan message only occur, if the function “use fan
as stage switching output” (SETUP/406) is deactivated (NO).
Pfc
/
off
The control is set inactive.
Pfc
/
Hold
The control is stopped.
NOTE:
Status messages cannot be reset by pressing the
(ESC) key.
NOTE:
Alarm messages are only displayed in the main menu. The menu items INFO, MANUAL, SETUP
or ALARM must not be selected.