TEMPERATURE SWITCH
-
OFF STAGES
The controller shall switch off the active stages depending on over-temperature in the switch cabinet.
Solution:
The CX plus is equipped with a temperature sensor (NTC) integrated under its housing. The
temperature limit for activation of the stage switch off sequence can be set in the alarm system. Hence,
the stages are protected against overheating and the temperature in the switch cabinet is able to cool
down to normal operation conditions.
Procedure:
Set the temperature limit 2 in the SETUP/513.
Set the temperature limit 2 in the SETUP menu. The temperature limit 1 (SETUP/512) may have to
be reduced because the minimum setting range of the temperature limit 2 depends on the set
temperature limit 1:
TEMP2
min
= TEMP1 + 5K
Activate the function
“
Switch off stage sequence in case of TEMP alarm
” (SETUP/503)
Activate the function
“
Switch off stage sequence in case of TEMP alarm
” (stage switch-off
sequence) in the
SETUP/503: SETUP/503 ==
YES
Time interval of the stage switch-off sequence (SETUP/523)
Set the time interval for the stage switch-off sequence under SETUP menu 523.
Function:
Upon exceeding temperature limit 2, a delay time of 10 s will expire first. Afterwards, the message
thi
ALARM
is displayed and the contact of the alarm relay is activated. After the time interval for the
stage switch-off sequence (SETUP/523) has run out, the stage switch-off sequence begins its
operation: The procedure switches off the relevant stage, which has been activated at last (AUTO,
FON). As long as the temperature alarm is activated, all active stages (AUTO, FON) are switched off
one by one in the cycle of the stage switch-off sequence. All stages which are switched off by the alarm
system are locked for a duration of 30 min. If all active stages have been switched off, the control is
stopped.
NOTE:
The alarm system does not switch off activated stages in manual operation mode. The stage
switch-off sequence does not start until the MANUAL menu is opened.
If the ambient temperature in the switch cabinet falls by 5 K below temperature limit 2 which has been
formerly setup, a still active stage switch-off sequence is cancelled. The control starts again and may
switch stages on and off again. The stages which have been switched off by the alarm system remain
locked for the duration of the blocking time and thus are not available for the control in the meantime.
If the function “Manual reset” (SETUP/501 = NO) is deactivated, the alarm messages (display and alarm
relay) are automatically reset after 15 s. The alarm relay is only reset, if no further alarm is active.
NOTE:
The stage switch-off function in case of TEMP alarm can be deactivated under menu
“digital
input alarm
” (SETUP/520 = NO). In case of a TEMP alarm, no activated stages will be switched off.
THD-U
/
THD-I
PROTECTION
In case the entire harmonic distortion of voltage (THD-U) or current (THD-I) is exceeded, the controller
shall protect the active stages by switch-off.
Solution: