wiring diagram (
no internal
connection
to the root
connection of the stage
switching outputs)
No display notification
I lo
ALARM
even though the measuring
current is less than 5 mA
I-LOW-alarm is suppressed
by the digital input.
Check the INFO display
under SETUP/519
“YES” == I-LOW-alarm is
suppressed by the digital
input. Do not trigger the
digital input, should the
occasion arise.
Check the setting for the
switching between
functions of the digital input
(SETUP/518), switch to
“NO”, if necessary.
Check the setting of logic
digital input (SETUP/511)
and switch to logic, if
necessary:
NO = LOW active
YES = HIGH active
No display notification
“
NT
”,
control does not work with target
COS-PHI 2, even though the
digital input is activated.
The function of the digital
input is not selected to
“Digital input switches to the
target COS
2
”.
Digital input logic is set
incorrectly.
Check the setting for the
switching between
functions of the digital input
(SETUP/518), switch to
“CP2”, if necessary.
Check the setting of logic
digital input (SETUP/511),
switch to logic, if necessary:
NO = LOW active
YES = HIGH active