Settings ALARM
MENU
FUNCTION
RANGE
501
Reset alarm manually
Yes/No
“
YES
”: Alarm messages (display and alarm relay) must be reset manually.
In order to reset active alarms,
keep
the key
(ESC)
pressed
for
approx.
3 s.
“
NO
”: As soon as the alarm condition is no longer active, the alarm
messages (display and alarm relay) is reset automatically.
NOTE:
An alarm can only be reset manually, if it is no longer active. The
alarm relay cannot be reset again until no alarm is active anymore.
502
THD-U limit value
3...20 %
Setting of the limit value for the THD-U monitoring.
If the set THD-U limit value is exceeded, the alarm is signalled (display and
alarm relay) after the set delay time (SETUP/ 504). The message
“
HarU
ALARM
” appears on the display. The alarm relay opens its contact.
If the function SETUP/503 is activated, all active stages (
“AUTO” & “FON”)
are switched off one by one referring to the switch-off interval set under
SETUP/523 and are locked for 30 min. The last active stage is switched off
first, when the switch-off interval has run out after the signalling of the alarm.
Then, the other stages are switched off one by one referring to the switch-
off interval. As all active stages have been switched off, the control stops for
as long as the alarm is still active.
If the value falls below the set THD-U limit value, a still active stage switch-
off sequence is cancelled. The already switched-off stages, however,
remain locked until the blocking time (max. 30 min) has run out. If the control
has been stopped, this is restarted and the controller can switch the stages
again. If the function
“Manual reset” (SETUP/501 = NO) is deactivated, the
alarm messages (display and alarm relay) are reset automatically after 15
s.
NOTE:
The control is stopped while the alarm is active. The stages which
have been switched off by the alarm system are locked for max. 30 min.
Active
“FON” stages are also switched off and blocked. Stages which have
been switched on manually are NOT switched off. If stages are switched off
manually, they are only locked until the discharge time is expired.
503
THD-U / THD-I / TEMP 2 alarm = switch off active stages
Yes/No
“
NO
”: active stages are not switched off in case of an alarm.
“
YES
”: If the configured THD-U or THD-I or TEMP 2 limit values is
exceeded, all active stages (
“AUTO” & “FON”) are switched off one by one
referring to the switch-off interval set under SETUP/523 and are locked for
30 min. The last active stage is switched off first, when the switch-off interval
has run out after the signalling of the alarm. Then, the other stages are
switched off one by one referring to the switch-off interval. As all active
stages have been switched off, the control stops for as long as the alarm is
still active.
NOTE:
The control is stopped while the alarm is still active. The stages
which have been switched off by the alarm system are locked for max. 30
min. Active
“FON” stages are also switched off and blocked. Stages which
have been switched on manually are NOT switched off. If stages are
switched off manually, they are only locked until the discharge time is
expired.
NOTE:
The digital input alarm can also lock the control system and initiate
the sequential deactivation of active stages.
504
Delay time THD-U- and THD-I-alarm
1...255 s