52
496234
5. Programming Reference
45-LEVEL ALM RSP
You can program each Level to give its own Alarm Response.
The responses available are:
LA-AR FU
(Full)
External Sounders (OP1 - timed, all other outputs as pro-
grammed).
Internal Sounders (Loudspeaker audible output).
Remote Signalling if plug-on communicator fitted and commu-
nications programmed.
LA-AR LO
(Local)
External Sounders (OP1 - timed, all other outputs as pro-
grammed).
Internal Sounders (Loudspeaker audible output).
NO signalling.
LA-AR IN
(Internal) Internal Sounders (Loudspeaker audible output).
46-REARM OPTIONS
To rearm a zone when the programmed bell duration ends, use this menu to
set the Level’s rearm response.
The rearm responses available are: 0, 1, 2, 3, AL (Never, Once, Twice, Three
Times, and Always).
At the end of the programmed bell duration the system checks all detectors
covered by the Level in alarm. The system omits open zones, and rearms
closed zones. If an open zone subsequently closes after the system rearms,
it will be reinstated.
47-KEYPA ALLOCN
This menu allows you to specify which keypads will give entry and exit tones
for individual Levels. The menu also allows you to enable or disable the PA
keys (1 and 3) and the control keys (7 and 9).
51-PROG OPUT TYP
Use this menu to program the output types. Note that the Bell output cannot
be changed to any outher output type, but the Strobe output can be repro-
grammed to another type.
24HL
(24 Hour Latch) This output will become active if a zone
designated as ’24 Hours’ is violated. The Level in which the 24
Hour zone is assigned to can be Set or Unset. The output will
remain active until the Level is disarmed by a valid user
access code.
808 sect 5 prog reference.p65
9/8/98, 10:28 AM
52