Functions of the heating circuit
Functions
WE
Configuration
Summer mode
0
01.06 - 30.09
2
1
18.0 °C
CO5 > F04 - 1
Time: Adjustable as required
No. days until activation: 1 to 3
No. days until deactivation: 1 to 3
Limit: 0.0 to 30.0 °C
Summer mode only becomes effective when the controller is in automatic mode ( ).
6.7 Delayed outdoor temperature adaptation
The calculated outdoor temperature is used to determine the flow temperature set point. The
heat response is delayed when the outdoor temperature either increases or decreases or
both. If the outdoor temperature varies by, for example 12 °C within a very short period of
time, the calculated outdoor temperature is adapted to the actual outdoor temperature in
small steps (delay time of 3 °C/h) over a time period of
.
The delayed outdoor temperature adaptation helps avoid unnecessary overloads of central
heating stations in combination with either overheated buildings occurring, for example due
to warm winds or temporarily insufficient heating due to the outdoor sensor being exposed
to direct sunshine. In the operating level, the outdoor temperature blinks on the display while
delayed outdoor temperature adaptation is active. A small hour glass appears next to the
thermometer on the display when this function is active. The calculated outdoor temperature
is displayed.
Functions
WE
Configuration
Delayed outdoor temperature adaptation
(decreasing)
0
CO5 > F05 - 1
Delay/h: 1.0 to 6.0 °C
Delayed outdoor temperature adaptation
(increasing)
0
3.0 °C
CO5 > F06 - 1
Delay/h: 1.0 to 6.0 °C
Note
Note