Functions of the heating circuit
6 Functions of the heating circuit
Which controller functions are available depends on the selected system code number (Anl).
6.1 Outdoor-temperature-controlled control
When outdoor-temperature-compensated control is used, the flow temperature is controlled
based on the outdoor temperature. The heating characteristic in the controller defines the
flow temperature set point as a function of the outdoor temperature (see Fig. 3). The outdoor
temperature required for outdoor-temperature-compensated control can either be measured
at an outdoor sensor or received over the 0 to 10 V input.
20
30
0.2
2.4
2.6
2.9
3.2
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.4
0.6
40
50
60
70
80
90
100
110
120
130
[°C]
–20
[°C]
–16
–12
–8
–4
0
4
8
12
16
20
140
150
–24 –28 –32 –36 –40
t
VL
t
A
t
VL
Flow temperature
t
A
Outdoor temperature
Fig. 3: Gradient characteristics
Functions
WE
Configuration
Outdoor sensor
0
CO1 > F02 - 1
0 to 10 V signal for outdoor temperature
0
Input
–20.0 °C
50.0 °C
CO5 > F23 - 1
Direction: Input
Lower transmission range: –50.0 to 100.0 °C
Upper transmission range: –50.0 to 100.0 °C