Functions of the heating circuit
6.8 Remote Control Unit
In addition to measuring the room temperature, the EGT333F102 remote control unit also
offers the option of setpoint correction: within nominal operation, the room setpoint can be
lowered or raised by up to 8.5 K using a continuously variable rotary knob. The middle
position is 21.5 °C.
When the room sensor is active, the measured room temperature value is displayed with the
remote control connected and activated, but not used for control if neither Optimization,
Adaptation or Short-Term Adaptation is activated.
Functions
WE
Configuration
Room sensor
0
CO1, 2 > F01 - 1
6.9 Optimization
This function requires the use of a room sensor. Depending on the building characteristics,
the controller determines and adapts the required advance heating time (maximum 8 hours)
to ensure that the desired 'Day set point' (rated room temperature) has been reached in the
reference room when the time-of-use starts. During the advance heating period, the controller
heats with the max. flow temperature. This temperature is built up in steps of 10 °C. As soon
as the 'Day set point' has been reached, outdoor-temperature-compensated control is activat-
ed.
Depending on the room sensor, the controller switches off the heating system up to one hour
before the time-of-use ends. The controller chooses the deactivation time such that the room
temperature does not drop significantly below the desired value until the time-of-use ends.
During the advance heating period and the premature deactivation of the heating system, the
or icon blink on the display.