EQJW146F002 EN
89
Functions of the heating circuit
Functions
WE
Configuration
Room sensor
0
CO1, 2 > F01 - 1
Flash adaptation
0
20 min
0.0
CO1, 2 > F09 - 1
Cycle time: 0 to 100 min
KP (gain): 0.0 to 25.0
Parameters
WE
Switch position: value range
Day set point
20.0 °C
: 0.0 to 40.0 °C
Night set point
15,0 °C
: 0.0 to 40.0 °C
6.10.1 Flash adaptation without outdoor sensor (based on room
temperature)
The flow temperature control starts with 'Day set point' for flow in rated operation or with
'Night set point' for flow in reduced operation as no set points calculated using characteris-
tics exist without an outdoor sensor. The 'Cycle time' determines the intervals at which the
flow temperature set point is corrected by 1 °C. The heating is then always switched off as
soon as the room temperature exceeds the 'Day set point' or 'Night set point' by 2 °C. Heat-
ing first starts again when the room has cooled off and the room temperature is 1 °C above
the set point. A 'KP (gain)' set to a value other than 0 causes a direct increase/decrease in
flow temperature set point when a sudden deviation in room temperature arises. A 'KP
(gain)' setting of 10.0 is recommended.
Functions
WE
Configuration
Room sensor
0
CO1, 2 > F01 - 1
Outdoor sensor
CO1 > F02 - 0
Flash adaptation
0
20 min
0.0
CO1, 2 > F09 - 1
Cycle time: 1 to 100 min
KP (gain): 0.0 to 25.0
Parameters
WE
Switch position: value range
Day set point
20.0 °C
: 0.0 to 40.0 °C
Night set point
15,0 °C
: 0.0 to 40.0 °C
Parameters
WE
Parameters: value range
Flow set point (day)
50.0 °C
PA1, 2 > P03: –5.0 to 150.0 °C
Flow set point (night)
30.0 °C
PA1, 2 > P04: –5.0 to 150.0 °C