EQJW146F002 EN
29
Start-up
The modifications of the controller configuration and parameter settings described in this sec-
tion can only be performed after the valid key number has been entered.
The key number that is valid on the first start-up can be found on page 165. To avoid unau-
thorized use of the service key number, remove the page or make the key number unread-
able. In addition, it is possible to enter a new, customized key number (see section 8.20).
3.1 Setting the system code number
31 different hydraulic schematics are available. Each system configuration is represented by
a system code number. The different schematics are dealt with in section 5. Available control-
ler functions are described in sections 6, 7 and 8.
Changing the system code number resets previously adjusted function blocks to their default
settings (WE). Function block parameters and parameter level settings remain unchanged.
The system code number is set in the configuration and parameter level.
Turn the rotary switch to (settings).
q
Enter the currently valid key number.
¼
Confirm key number.
q
Select 'System'.
¼
Open 'System'.
q
Select the required system.
Содержание EQJW146F002
Страница 2: ...2 EQJW146F002 EN ...
Страница 125: ...EQJW146F002 EN 125 Installation 1 2 2 5 3 4 5 62 15 41 57 Panel mounting Wall mounting Rail mounting Fig 9 Installation ...
Страница 158: ...158 EQJW146F002 EN ...
Страница 159: ......