138
EQJW146F002 EN
Appendix
CO5: System-wide functions (all systems)
If the controller indicates CO5 > F00 - 1, any access to the return flow, flow rate and capaci-
ty settings is locked.
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01 Sensor type
1
1
0
All*
CO5 > F01 - 1, F02 - 0: Pt 1000
CO5 > F01 - 0, F02 - 0: PTC
CO5 > F01 - 1, F02 - 1: Ni 1000
02
03
04 Summer mode
0
Not sys-
tems Anl
1.5, 1.6,
1.9, 3.5
CO5 > F04 - 1: Summer mode
Function block parameters:
Time: Adjustable as required (01.06. - 30.09.)
No. days until activation: 1 to 3 (2)
No. days until deactivation: 1 to 3 (1)
Limit: 0.0 to 30.0 °C (18.0 °C)
05 Delayed out-
door tempera-
ture adaptation
(decreasing)
0
Not Anl
1.9
CO5 > F05 - 1: Delayed outdoor temperature adaptation as
the temperature falls
Function block parameters:
Delay/h: 1.0 to 6.0 °C (3.0 °C)
06 Delayed out-
door tempera-
ture adaptation
(increasing)
0
Not Anl
1.9
CO5 > F06 - 1: Delayed outdoor temperature adaptation as
the temperature rises
Function block parameters:
Delay/h: 1.0 to 6.0 °C (3.0 °C)
07 Error message
0
Not Anl 4.1,
4.5, 11.1,
11.2, 11.3,
11.6, 16.1,
16.6
CO5 > F07 - 1: Terminal for error message: see plant scheme
table
Function block parameters:
Relay contact = NO contact, NC contact (NO contact)
08 Summer time
0
All
CO5 > F08 - 1: Summer/standard time switchover
09 Frost protection
1
Not sys-
tems Anl
1.5, 1.6,
1.9, 3.5
CO5 > F09 - 1: Highest priority for frost protection
Function block parameters:
Limit: –15.0 to 3.0 °C (3.0 °C)
CO5 > F09 - 0: Restricted frost protection
Function block parameters:
Limit: –15.0 to 3.0 °C (3.0 °C)
0
1.5, 1.6,
1.9, 3.5