140
EQJW146F002 EN
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
24 0-10 V input
0
All
CO5 > F24 - 1: The measured value at 0 to 10 V input is dis-
played as a special value.
25 AA1 reverse
0
All
CO5 > F25 - 0: 0 V/0 % = Valve CLOSED/pump OFF
CO5 > F25 - 1: 0 V/0 % = Valve OPEN/pump with max. de-
livery rate
Function block parameters:
Zero: 0 to 50 % (0 %)
31 AI1 Zero shift
0
All*
CO5 > F31 - 0
Function block parameters:
Zero: 5 to 20 % (5 %)
F Function block number, WE Default setting, Anl System code number
CO6 > Modbus (all systems)
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01 Modbus
1
All
CO6 > F01 - 1: Modbus active
02 16-bit address
0
All
CO6 > F02 - 1: Modbus 16-bit addressing
(only with CO6 > F01 - 1)
CO6 > F02 - 0: Modbus 8-bit addressing
03 Modem
0
All
CO6 > F03 ... F06 is required to configure the error message
transfer to a connected Modbus/GPRS gateway (1402-0701).
04 Automatic con-
figuration
0
All
05 Lock dial-up to
building auto-
mation system
0
All
06 Dial-up also
upon corrected
error
0
All
07 Monitoring
0
All
CO6 > F07 - 1: Control system monitoring > Resets all level bits
to “autonomous“ when there is no communication(only with
CO6 > F01 - 1)
08 Text message
0
All
CO6 > F06 is required to configure the error message transfer
to a connected Modbus/GPRS gateway (1402-0701).