EQJW146F002 EN
153
Appendix
P
Parameters
PA1 (HC1)
PA2 (HC2)
Value range
05 Return flow temperature, point 3
5.0 to 90.0 °C
Return flow temperature, point 4
5.0 to 90.0 °C
Flow rate, point 1
–
0.01 to 650 m³/h
Flow rate, point 2
–
0.01 to 650 m³/h
Flow rate, point 3
–
0.01 to 650 m³/h
Flow rate, point 4
–
0.01 to 650 m³/h
06 Min. flow temperature
–5.0 to 150.0 °C
07 Max. flow temperature
5.0 to 150.0 °C
09 Outdoor temperature for continuous
day mode
–50.0 to 5.0 °C
10 Minimum flow temperature set point
HC for binary demand processing
5.0 to 150.0 °C
11 Return flow gradient
0.2 to 3.2
12 Return flow level
–30.0 to 30.0 °C
13 Base point for return flow temperature:
5.0 to 90.0 °C
14 Max. return flow temperature
5.0 to 90.0 °C
15 Set point boost (pre-control circuit)
0.0 to 50.0 °C
16 Minimum set point to charge buffer
tank
–
OT to 90.0 °C
17 Stop charging of the buffer tank
–
OT to 90.0 °C
18 Charging temperature boost
–
0.0 to 50.0 °C
19 Lag time of charging pump
–
0.0 to 10.0
CO1 function block parameters (heating circuit HC1) and CO2 function block parameters
(heating circuit HC2)
F
Function block parameters
CO1 (HC1)
CO2 (HC2)
Value range
03 KP (limiting factor)
0.1 to 10.0
05 Start temperature
20.0 to 60.0 °C
05 Hold (days)
0 to 10 days
05 Temp. rise/day
0.0 to 10.0 °C
05 Maximum temperature
25.0 to 60.0 °C
05 Hold (days)
0 to 10 days
05 Temp. reduction/day
0.0 to 10.0 °C
05 Start condition
Start, Stop, Hold, Re-
duction
09 Cycle time
0 to 100 min