154
EQJW146F002 EN
Appendix
F
Function block parameters
CO1 (HC1)
CO2 (HC2)
Value range
09 KP (gain)
0.0 to 25.0
12 KP (gain)
0.1 to 50.0
12 Tn (reset time)
1 to 999 s
12 TV (derivative-action time)
0 to 999 s
12 TY (valve transit time)
15 to 240 s
12 Hysteresis
1.0 to 30.0 °C
12 Min. ON time
0 to 10 min
12 Min. OFF time
0 to 10 min
13 Max. system deviation
3.0 to 10.0 °C
14 Active when BI =
ON, OFF
16 Lower transmission range
0.0 to 150.0 °C
16 Upper transmission range
0.0 to 150.0 °C
17 Active when BI =
ON, OFF
18 Lower transmission range
–
0.0 to 150.0 °C
18 Upper transmission range
–
0.0 to 150.0 °C
18 Boost
0.0 to 30.0 °C
21 Start speed reduction - SF2 limit
–
5.0 to 90.0 °C
21 Stop speed reduction - SF2 limit
–
5.0 to 90.0 °C
21 Minimum speed
–
0 to 50 %
23 Set point of differential temperature
control
–
0.0 to 50.0 °C
23 KP (influence factor)
–
0.1 to 10.0
23 Minimum speed
–
0 to 100 %
PA4 parameters (domestic hot water heating)
P
Parameters
PA4 (DHW)
Value range
01 Min. adjustable DHW set point
5.0 to 90.0 °C
02 Max. adjustable DHW set point
5.0 to 90.0 °C
03 Hysteresis
1.0 to 30.0 °C
04 Charging temperature boost
0.0 to 50.0 °C
05 Max. charging temperature
20.0 to 150.0 °C
06 Lag time for storage tank charging
pump
0.0 to 10.0 x valve transit time
07 Max. return flow temperature
20.0 to 90.0 °C
10 Solar circuit pump ON
0.0 to 30.0 °C
11 Solar circuit pump OFF
20.0 to 90.0 °C