Functions of the DHW circuit
7.3 DHW heating in instantaneous heating system
WW
VF
ZP
KW
VF
Flow sensor
ZP
Circulation pump (DHW)
WW Hot water
KW
Cold water
WW
VF
ZP
KW
Water flow sensor
Fig. 8: Schematics of an instantaneous heating system
Without flow rate sensor or flow switch, the control of the required DHW temperature at the
flow sensor VF is only active during times-of-use of the circulation pump ZP. The flow rate
sensor or flow switch allows the controller to recognize when DHW tapping starts and stops.
Control of the required DHW temperature can made to be active only during DHW tapping
by deleting all times-of-use of the circulation pump.
The control of the required DHW temperature at the flow sensor VF is only active during
times-of-use of the circulation pump ZP.
Functions
WE
Configuration
Flow rate sensor
0
Analog
CO4 > F04 - 1
Selection: Analog (flow rate sensor), binary
(flow switch)
Parameters
WE
Switch position: value range
Day set point for DHW temperature
60.0 °C
: Min. to max. adjustable DHW set point
Night set point for DHW temperature
40.0 °C
: Min. to max. adjustable DHW set point
Parameters
WE
Parameters: value range
Min. adjustable DHW set point
40.0 °C
PA4 > P01: 5.0 to 90.0 °C
Max. adjustable DHW set point
60.0 °C
PA4 > P02: 5.0 to 90.0 °C