88
EQJW146F002 EN
Functions of the heating circuit
Outside the times-of-use, the controller monitors the 'Night set point' (reduced room tem-
perature). When the temperature falls below the night set point, the controller heats with the
max. flow temperature until the measured room temperature exceeds the adjusted value by
1 °C.
− Direct sunshine can cause the room temperature to increase and thus result in the prema-
ture deactivation of the heating system.
− When the room temperature decreases while the heating system is shortly outside its times-
of-use, this can prematurely cause the controller to heat up to the 'Day set point'.
Functions
WE
Configuration
Room sensor
0
CO1, 2 > F01 - 1
Outdoor sensor
CO1 > F02 - 1
Optimization
0
CO1, 2 > F07 - 1
Parameters
WE
Switch position: value range
Day set point
20.0 °C
: 0.0 to 40.0 °C
Night set point
15,0 °C
: 0.0 to 40.0 °C
6.10 Flash adaptation
To ensure that the controller reacts immediately to room temperature deviations during rated
or reduced operation, the function block setting CO1, 2 > F09 - 1 needs to be made. The
heating is then always switched off as soon as the room temperature exceeds the 'Day set
point' or 'Night set point' by 2 °C.
Heating first starts again when the room has cooled off and the room temperature is 1 °C
above the set point. The flow temperature set point is corrected if the 'Cycle time' and 'KP
(gain)' are set to a value other than 0. The 'Cycle time' determines the intervals at which the
flow temperature set point is corrected by 1 °C. A 'KP (gain)' set to a value other than 0
causes a direct increase/decrease in flow temperature set point when a sudden deviation in
room temperature arises. A 'KP (gain)' setting of 10.0 is recommended.
− Cooling loads, such as drafts or open windows, affect the control process.
− Rooms may be temporarily overheated after the cooling load has been eliminated.
Note
Note