Design of Mini ECO-i SYSTEM
2. System Design
2-7. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-7 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size
Amount of refrigerant
charge/m (g/m)
ø6.35
26
ø9.52
56
Required amount of charge = (Amount of refrigerant
charge per meter of each size of liquid tube
×
its tube
length) + (...) + (...)
*Always charge accurately using a scale for weighing.
Table 2-8 Refrigerant Charge Amount at Shipment (for outdoor unit)
2-8. System Limitations
Table 2-9 System Limitations
N
u
mber of max. co
nn
ectable i
n
door
un
it
s
O
u
tdoor
un
it
s
(Type)
3
65
6
4
8
5
8
605
9
Max. allowable i
n
door/o
u
tdoor capacity ratio
50 1
3
0
%
Heat p
u
mp
un
it
S
PW-CR
3
65GXH56
3
.5
S
PW-CR
3
65GX56
3
.5
S
PW-CR4
8
5GXH56
3
.5
S
PW-CR4
8
5GX56
3
.5
S
PW-CR605GXH56
3
.5
S
PW-CR605GX56
3
.5
(k
g
)
(k
g
)
Cooli
ng
o
n
ly
un
it
2-9. Tubing Length
R410A distribution joint
APR-RP160AG (for indoor unit)
Note: Do not use commercially available T-joints for the liquid tubing.
H2
LD
L1
L2
LC
LB
LA
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.
Main tube of unit
1st branch
Unit distribution tube
1
2
3
n-1
n
L3
H1
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 15
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...