Control of Mini ECO-i SYSTEM
1. Main Operating Functions
1-1. Room Temperature Control
The thermostat is turned ON/OFF according to
L
T as shown below.
* Intake shift temperature (enabled only during heating)
During heating, a difference in temperature occurs between the top and bottom of a room. This value is set in
consideration for the difference between the temperature detected by the body sensor and the temperature at the
bottom of the room.
<Value set for intake shift temperature at time of shipment>: 4°C
Note:
The shift temperature can be selected in the range of 0 – 10°C, by using the remote controller simplified
setting mode.
(1) After the thermostat turns ON, it will not turn OFF again as a result of
L
T for 5 minutes.
(2) After the thermostat turns OFF, it will not turn ON again for 3 minutes. (It also will not turn ON for 3 minutes
after the power is switched ON.)
(3) The compressor turns OFF if the mode is changed cooling
→
heating (or heating
→
cooling) while the com-
pressor is ON.
(4) If “test run” mode is selected, the thermostat will not turn OFF as a result of
L
T for 60 minutes. (The thermo-
stat is forced ON.)
L
T = Room temperature - Set temperature
When remote controller
sensor is used
Room temperature = Temperature detected by the remote controller sensor
When body sensor is used
Room temperature = Temperature detected by the body sensor - Intake shift temperature*
Cooling
Heating
Room temperature
Room temperature
Set temperature
–1
+1
+2
(deg)
T
Set temperature
–2
–1
+1
(deg)
T
Thermostat
ON
ON
OFF
Thermostat
ON
ON
OFF
06-405 Mini-ECOi_TD3 11/6/06 6:18 PM Page 3
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...