5
- 12
5
Test Run and Others
2. Test Run
Automatic Address Setting (no compressor operation)
G
Indoor and outdoor unit power can be turned ON for each system separately.
Indoor unit addresses can be set without operating the compressors.
Automatic Address Setting from Outdoor Unit
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the
DIP switch (S003) is set to “0.”
(These are the settings at the time of factory shipment.)
2. To set the number of indoor units that are connected to the outdoor unit to 6, on the outdoor unit control PCB set
the No. of indoor units rotary switch (S004) to “6.”
3. At the outdoor unit where all indoor and outdoor unit power has been turned ON, short-circuit the automatic
address pin (CN51) for 1 second or longer, then pull it out.
↓
(Communication for automatic address setting begins.)
↓
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)
↓
4. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 – 3
in the same way to complete automatic address settings for all systems.
↓
5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller
complete automatic address setting.
Refer to “Automatic Address Setting from the Remote Controller.”
ON
ON
OFF
1
2
Case 1
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
06-405 Mini-ECOi_TD5 11/6/06 5:01 PM Page 12
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...