Design of Mini ECO-i SYSTEM
1. Model Selecting and Capacity Calculator
Table 1
Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
ø15.88
ø19.05
0.4
* When increasing the size of the gas tubing (LM), multiply by the correction coefficient from Table 1 and calculate the
equivalent length for section LM.
Tubing equivalent length after size increase = Standard tubing equivalent length
×
Equivalent length correction coefficient
Tube diameter after change (gas tube, mm)
Equivalent length correction coefficient
Standard tube diameter (gas tube, mm)
For CR365, 485GX(H)56 units
I
If the maximum tubing length (L1) exceeds 90 m (equivalent length), increase the tubing size of the main gas
tube (LM) by one rank.
* The size increase is applied to the gas tube only. In addition, for a 6 HP unit it is not necessary to increase the
tubing size.
I
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 1 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The size increase is applied to the LM gas tube (main tube with the largest diameter) only, and is limited to the
cases shown in Table 1. In addition, the amount of additional refrigerant charge is determined from the liquid-
tube size only.
* In case of 6PS, increasing the size of the gas tube is not possible.
The upper limit for tubing size is ø19.05. Tubing above that size cannot be used.
WARNING
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 12
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...