3
3
- 33
Control of Mini ECO-i SYSTEM
3. Wired Remote Controller
I
Basic Wiring Diagram
CAUTION
Install wiring correctly
(incorrect wiring will dam-
age the equipment).
G
Use shielded wires for remote control wiring and
ground the shield on both sides. Otherwise misop-
eration due to electrical noise may occur.
Shielded wire
Ground
1 2
1
1 2
1 2
1
1 2
1
1 2
1
: Ground
Outdoor unit
Indoor unit
No. 8
Indoor unit
No. 3
Indoor unit
No. 2
Indoor unit
No. 1
1
Group
control
Connection wiring
for group control
Standard
remote control
Multiple
remote control
1
1
1
Inter-unit control wiring
Terminal
3P
2
2
2
2
2
2
2
2
Remote
control wiring
Inter-unit wiring
Group-control wiring
(Main) (Sub)
Indoor
unit 8
Indoor
unit 7
Indoor
unit 2
Indoor
unit 1
I
Wiring System Diagram for Group Control
This diagram shows when several units (maximum of
8) are controlled by a remote controller (main unit). In
this case, a remote controller can be connected at
any indoor unit.
Wiring procedure
Wire according to the diagram at right:
G
Each successive unit will respond at 1-second
intervals following the order of the group address
when the remote controller is operated.
Group control using 2 remote controllers
It does not matter which of the 2 remote controllers
you set as the main controller.
When using multiple remote controllers (up to 2 can
be used), one serves as the main remote controller
and the other as the sub-remote controller.
1 2
1
1 2
1 2
1
1 2
1
1 2
1
Outdoor unit
Indoor unit
No. 8
Indoor unit
No. 3
Indoor unit
No. 2
Indoor unit
No. 1
1
Remote
controller
Connection wiring for
group control
Inter-unit
control
wiring
Terminal
3P
2
2
2
2
2
(sub)
3P terminal
base for remote
control wiring
Remote
controller
(main)
1
Indoor unit
No. 1
: Ground (earth)
Indoor unit
No. 2
Indoor unit
No. 8
Indoor unit
No. 3
Connection wiring
for group control
1
1
1 2
2
2
2
1
2
1
2
06-405 Mini-ECOi_TD3 11/6/06 6:18 PM Page 33
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...