5
- 16
5
Test Run and Others
2. Test Run
Request concerning recording the indoor/outdoor unit combination Nos.
After automatic address setting has been completed, be sure to record them for future reference.
List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible location
(next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3…
(Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3…
These numbers are necessary for later maintenance. Please be sure to indicate them.
Checking the indoor unit addresses
Use the remote controller to check the indoor unit address.
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the
button and
button for 4 seconds or longer (simple settings mode).
2. The address is displayed for the indoor unit that is connected to the remote controller.
(Only the address of the indoor unit that is connected to the remote controller can be checked.)
3. Press the
button again to return to normal remote controller mode.
<If multiple indoor units are connected to 1 remote controller (group control)>
1. Press and hold the
button and
button for 4 seconds or longer (simple settings mode).
2. “ALL” is displayed on the remote controller.
3. Next, press the
button.
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan
of that indoor unit starts and that air is discharged.
5. Press the
button again and check the address of each indoor unit in sequence.
6. Press the
button again to return to normal remote controller mode.
Remote Controller Test Run Settings
1. Press the remote controller
button for 4 seconds or longer. Then press the
button.
G
“TEST” appears on the LCD display while the test run is in progress.
G
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.
Note:
The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after
operation is stopped.
3. If correct operation is not possible, a code is displayed on the remote controller display.
(Refer to “2-6. Meaning of Alarm Messages” and correct the problem.)
4. After the test run is completed, press the
button again. Check that “TEST” disappears from the remote con-
troller display.
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after
60 minutes.)
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceil-
ing panel has not been installed. (“P09” display does not occur.)
Indoor unit address
Number changes to indicate which indoor unit is currently selected.
06-405 Mini-ECOi_TD5 11/6/06 5:01 PM Page 16
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...