Design of Mini ECO-i SYSTEM
1. Model Selecting and Capacity Calculator
1-3. Calculation of Actual Capacity of Indoor Unit
I
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length,
elevation difference and other factors, select the correct model after taking into account the various correction val-
ues. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the
corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final
capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit temperature conditions
From the graph of capacity characteristics on page 2-6, use the outdoor temperature to find the capacity correc-
tion coefficient.
(2) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-7, use the tubing length and elevation difference
to find the capacity correction coefficient.
The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(3) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-7, find the capacity correction coefficient.
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-8, use the indoor temperature to find the capacity correc-
tion coefficient.
(2) Capacity distribution ratio based on the indoor unit tubing length and elevation difference
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit
to find the correction coefficient from the graph of capacity change characteristics on page 2-8. Then divide the
result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit.
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
G
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity
×
Correction coefficient for out-
door temperature conditions ((1) Page 2-6)
×
Correction coefficient
for tubing length and elevation difference ((2) Page 2-8)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
G
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit
×
Correction coef-
ficient for indoor temperature conditions at that indoor unit ((1) Page 2-7)
×
Distribution ratio based on tubing
length and elevation difference at that indoor unit ((2) Page 2-8)
However, the corrected cooling capacity of each indoor unit is found as shown below.
If (1) < 100% and (1)
×
(2) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit
If (1)
≥
100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit
×
(1)
Capacity distribution ratio for each indoor unit (2) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni
t
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 4
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...