2
2
- 26
Design of Mini ECO-i SYSTEM
3. Installation Instructions
3-2. Outdoor Unit
AVOID:
G
heat sources, exhaust fans, etc. (Fig. 2-6)
G
damp, humid or uneven locations
DO:
G
choose a place as cool as possible.
G
choose a place that is well ventilated and outside air temperature
does not exceed maximum 45°C constantly.
G
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-7)
G
use lug bolts or equal to bolt down unit, reducing vibration and noise.
Installation space
Distance between obstructions and the unit air inlet and outlet must be
as shown below.
Fig. 2-6
Fig. 2-8
Fig. 2-9
Out-
door
unit
Heat source
Hot air
Exhaust fan
Anchor bolts
(4 pieces)
In case of multiple installations
G
provide a solid base (concrete block, 10
×
40 cm
beams or equal), a minimum of 15 cm above
ground level to reduce humidity and protect the unit
against possible water damage and decreased
service life. (Fig. 2-9)
G
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
*4
*1
*2
*3
*1
More than 1 cm
More than
100 cm
More than 1 cm
Inlet side C
Inlet side
More than 20 cm
Outlet side
(field supply)
A
B
(Ground)
Air direction chamber
(Obstruction above unit)
(Obstruction on
inlet side)
CAUTION
G
Concerning inlet-side distance “C” (Fig. 2-7)
The minimum for distance “C” is 15 cm if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 20 cm.
G
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.
G
If wall *1 is on the outlet side (Fig. 2-7), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 2-7), then the minimum distance for “A” and “B” is 2 m (Fig. 2-9). Even
if there is no wall on the outlet side, a minimum of 100 cm is required.
Fig. 2-7
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 26
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...