Design of Mini ECO-i SYSTEM
3. Installation Instructions
Fig. 2-10
Fig. 2-11
Fig. 2-12
3-3. Air Discharge Chamber for Top Discharge
Be sure to install an air discharge chamber in the
field when:
G
it is difficult to keep a space of min. 50 cm between
the air discharge outlet and an obstacle.
G
the air discharge outlet is facing a sidewalk and
discharged hot air may annoy passers-by.
Refer to Fig. 2-10.
3-4. Installing the Unit in Heavy Snow Areas
In locations with strong wind, snow-proof ducting
should be fitted and direct exposure to the wind
should be avoided as much as possible.
I
Countermeasures against snow and wind
In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not
provided with a platform and snow-proof ducting:
a) The outdoor fan may not run and damage to the
unit may occur.
b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
3-5. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow
depth. (Fig. 2-11)
(2) The 2 anchoring feet of the outdoor unit should be
used for the platform, and the platform should be
installed beneath the air intake side of outdoor
unit.
(3) The platform foundation must be firm and the unit
must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent
the unit from being blown over.
Air di
s
char
g
e
In regions with significant snowfall, the outdoor unit should
be provided with a platform and snow-proof duct.
Without snow-
proof ducting
(Low platform)
With snow-
proof ducting
(High platform)
Outdoor
Duct
Air
Unit
intake
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 27
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...