4
4
- 130
Mini ECO-i SYSTEM Unit Specifications
8. Concealed Duct High Static Pressure Type (D Type)
8-2. Major Component Specifications
Indoor unit (A)
MODEL No.
SPW-DR254GXH56(A/B)
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
Controller P.C.B. Ass’y
CR-TRP50A-B (Microprocessor)
Fan (Number…diameter)
mm
Centrifugal (1 … ø 220)
Fan motor
Model…Nominal output
W
KFC4X-201B5P … 200 W
Power source
220 - 230 - 240 V / Single-phase / 50 Hz
No. of pole…r.p.m. (230 V, High)
rpm
4P … 1,004
Coil resistance
Ω
BRN – WHT :
13.75
ORG – YEL
:
2.21
(Ambient temperature 20
°
C)
WHT – VLT
:
4.47
YEL – BLK
BLK – PNK
:
:
10.33
12.90
VLT – ORG :
1.20
Safety device
Operating temperature
Open
°
C
130
±
5
(115
±
5)
Close
°
C
Run capacitor
VAC,
µ
F
440 VAC, 5.0
µ
F
Electronic expansion valve
Coil
UKV-U030E
Coil resistance (at 20
°
C)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-25D32
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows…fin pitch
mm
3…2.0
Face area
m
2
0.233