3
Control of Mini ECO-i SYSTEM
5. Schedule Timer
Fig. 3-48
Schedule
timer
Field supply
Communication
wiring
(pink + blue)
Power wiring
(white & black)
System controller
(Back side)
Inter-unit control wiring
G
Wiring
The schedule timer wiring can be connected by the following two methods. Select one of these connection meth-
ods according to the actual installation location.
When wiring, extend the lengths of the wires using wire joints (provided) and extension wires (field supply).
G
Connection diagram (Be sure to use the provided wires as the power wiring.)
If a system controller is also installed:
CAUTION
When installing multiple schedule timers, avoid
the use of cross-over wiring.
If power is supplied from the indoor unit control PCB of a nearby indoor unit, connect the provided T10 terminal
connection wires to the T10 terminal on the indoor unit control PCB, and to the schedule timer power wires.
G
The inter-unit control wiring has no polarity. The wiring may be connected in either direction to U1 and U2.
G
If necessary, use a relay wire when connecting the wiring to the indoor unit control PCB.
G
The power wiring has no polarity. The wiring may be connected in reverse.
G
The length of the power wiring must be no more than 200 m.
Connect the wires for the schedule timer inter-unit control wiring (see Note below) to the C1 and C2 terminals on
the system controller terminal board. Connect the system controller power wiring to CN02 and to the schedule
timer power wires (white + black).
G
The inter-unit control wiring has no polarity. The wiring may be connected in either direction to C1 and C2.
G
The power wiring has no polarity. The wiring may be connected in reverse.
G
The length of the power wiring must be no more than 100 m.
Note:
The inter-unit control wires are pink + blue + blue (using wire joint crimping). Use pink + blue wires.
If a system controller is not installed (power is supplied
from the indoor unit):
Fig. 3-49
T10
U1
U2
Indoor unit control
PCB
Inter-unit
control wiring
Schedule
timer
Communication
wiring (pink + blue)
Power wiring
(white + black)
Field supply
Indoor unit
1
NOTE
The only functions of the schedule timer are indoor unit ON/OFF and remote controller enable/disable
operations. It is therefore recommended that during installation, a system controller, remote controller,
or similar device be installed next to the schedule timer so that the operation mode and other informa-
tion can be checked.
(If the system controller or other central control device is not present, the schedule timer cannot be
used in combination with a system that does not utilize remote controllers.)
3
- 81
06-405 Mini-ECOi_TD3 11/6/06 6:18 PM Page 81
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...