4
4
- 126
Mini ECO-i SYSTEM Unit Specifications
7. Concealed Duct Type (U Type)
7-5. Increasing the Fan Speed
If external static pressure is too great (due to long
extension of ducts, for example), the air flow volume
may drop too low at each air outlet. This problem may
be solved by increasing the fan speed using the
following procedure:
(1)
Remove 2 screws on the electrical component
box and remove the cover plate.
(2)
Disconnect the fan motor sockets in the box.
(3)
Take out the booster cable (sockets at both ends)
clamped in the box.
(4)
Securely connect the booster cable sockets
between the disconnected fan motor sockets in
step 2 as shown in the Fig. 7-1.
(5)
Place the cable neatly in the box and reinstall the
cover plate.
Booster cable
Booster cable
Electrical component box
(At shipment)
(Connected booster cable)
1743_M_I
Fan motor socket
Fan
motor
Indoor Fan Performance
25 Type
48 Type
36 Type
Fig. 7-2
20
Air Flow Volume (m
3
/minute)
External Static Pressure
0
50
0
5
10
15
150
10
Limit line
Limit line
HT
H
L
100
I
M
(mmAq)
(Pa)
30
25
40
Air Flow Volume (m
3
/minute)
External Static Pressure
0
50
0
5
5.6
3.8
10
15
150
20
Limit line
Limit line
L
100
M
H
(mmAq)
(Pa)
HT
30
Air Flow Volume (m
3
/minute)
External Static Pressure
0
50
0
5
6.6
5.4
2.4
3.7
14 16
10
15
150
20
21
26
Limit line
HT
L
100
M
H
Limit line
(mmAq)
(Pa)
HT : Using the booster cable
H : At shipment
NOTE
■
How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (m
3
/minute). The
characteristic curves for “HT”, “H”, “M” and “L” fan speed control are shown.
The nameplate values are shown based on the “H” air flow. For the 25 type, the air flow is 18 m
3
/minute, while the
external static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of duct, for
example), the air flow volume may drop too low at each air outlet.
This problem may be solved by increasing the fan speed as explained above.
Fig. 7-1
16, 18 Type
7, 9, 12 Type
5
7
8.5
Air Flow (m
3
/minute)
External Static Pressure
0
50
100
0
5
4.4
4.9
10
15
150
10
(mmAq)
(Pa)
Limit line
Limit line
HT
H
M
L
15
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
2.5
3.9
10
15
150
10
10.5
9
12
Limit line
Li
mit line
HT
M
L
100
H
(mmAq)
(Pa)
06-405 Mini-ECOi_TD4 11/8/06 4:28 PM Page 126
Содержание SPW-CR365GX56
Страница 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Страница 8: ...1 4 MEMO ...
Страница 322: ...4 180 MEMO ...
Страница 330: ...CN33 S003 CN51 CN50 D043 LED2 D042 LED1 S002 S004 5 8 Test Run and Others 2 Test Run Fig 5 10 2 for SPW CR GX H 8 5 ...
Страница 344: ...5 22 MEMO ...
Страница 345: ...200611M DC ...