Extra indication contacts S5
[r5]
, S6
[r6]
, S7
[r7]
and S8
[r8]
are available as
an option.
Check actuator circuit diagram for
inclusion.
When the Extra Contact Option is
included the set-up procedure and
available contact functions for S5 – S8
are identical to S1–S4
(refer to Section
9.2 page 28)
.
Unless specified with order the default
setting for the extra indication contacts
will be as follows:
S5
[r5]
Close limit indication
S6
[r6]
Open limit indication
S7
[r7]
Torque trip mid travel
S8
[r8]
Remote control selected
NOTE:
If the Extra Contact Option is
not included in the actuator build, any
settings made for S5–S8 will have no
effect on the indication output of the
actuator.
The action of turning on the Extra
Contact Option makes an additional
series of set-up screens available
Enabled Disabled
Extra Contact Set-up Displays
Press the
+
or
-
key to select the Extra
Contact Option set-up screens
[O
n
]
.
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
PRESS THE
Q
KEY TO ACCESS S5
TO S8 SET-UP DISPLAYS.
The procedure for setting S5 to S8
is the same as that for S1 to S4
(refer to Section 9.2 page 28)
.
33
9.4
Option Extra
Indication Contacts
OE
Display Extra Contact
Set-up Screens