Using the
+
or
-
key select the position
for the
TIMER TO STOP WHEN THE
VALVE IS OPENING.
[
] [
]
= valve closed
[01]
to
[99]
= percentage open
[
]
= valve open
Timer Set to Stop Pulsing
when Opening Valve
Reaches 25% Open
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
If timing is not required in the opening
stroke select
[JO]
to
[
] [
]
.
Press the
O
key to display
[Jn]
.
Using the
+
or
-
key select the actuator
run period in the range 1–99 seconds.
Actuator Run Period
Set for 5 Seconds
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
Press the
O
key to display
[JF]
.
Using the
+
or
-
key select the actuator
stop period in the range 1–99 seconds.
Actuator OFF Period
Set for 25 Seconds
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
Press the
O
key to display
[JE]
(refer
to note on Page 58)
.
The interrupter timer may be overridden
when the actuator is under ESD signal
command. This will mean the actuator
will run to limit without “stop/start”
action under ESD command.
Refer to A1–A3
(refer to page 30 for
ESD settings)
.
The default for ESD override interrupter
timer is
[OF]
. The interrupter timer will
continue “stop/start” action during ESD
action.
If ESD must override the timer use the
+
or
-
to display
[O
n
]
.
ESD Override Timer OFF
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
57
JO
Position in Valve Opening
Stroke for Timer to Stop
Contactor On Time
Jn
Contactor Off Time
JF
JE
ESD Override
Interrupter Timer