Setting instructions for actuators
including an optional Profibus DP
module – check wiring diagram for
inclusion.
Before setting the parameters for
Option Profibus ensure Remote
Control Source [Od] has been
selected to [oP] in Section 9.7.
Profibus module set-up screens can be
turned off to provide extra security. The
action of turning screens on or off does
not affect its operation.
Use the
+
or
-
keys to turn on Profibus
set-up screens.
Profibus set-up screens
[O
n
]
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
Press the
Q
key to display the Profibus
set-up screens.
The Profibus DP module must be
allocated a unique address.
To set the address the Profibus module
must be isolated from the host by
disconnecting the RS485 highway or
turning off the host device.
Using the
+
or
-
keys display the
required address.
Address to be set within the range 01
to 7E Hexadecimal
(refer to page 72 for
conversion)
. If an address value outside
this range is entered, the address set
will revert to 01 (for 00) or 7E (for value
above 7E).
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
Press the
O
to display
[Pb]
.
47
9.10
Bus System
Option Profibus DP [OP]
Profibus Address
PA