With
[Ab]
displayed
Use the
+
and
-
key to select the
required actuator type. The selectable
values are related to actuator type as
follows:
Value
Type
1 IQT125
3 IQT250
6 IQT500
12 IQT1000
24 IQT2000
PRESS THE
KEY.
The displayed value will flash,
indicating that it has been set.
Any value of hex outside of the range
stated will not be accepted into the
actuator memory.
NOTE:
Mains power has to be on for
actuator type setting to be carried out.
59
Actuator Type Setting
9.16
Positional Display
Q
Q
P?
O
PC
O
Ir
O
Ic
Q
Contact Function
cr
O
Contact S1
r1
Q
Contact S2
r2
Q
Contact S3
r3
Q
Contact S4
r4
Q
ESD Action
Control Mode
Configuration
A1
Q
Extra Indication
Folomatic
Remote
Bus
Contacts
CPT
Remote Control
Control Source
System
Option Selection
OE
O
OI
O
OF
O
Od
O
OP
Q
PA
Q
O
50
IrDA
comms
Primary
Functions
IQT Speed
Setting
AA
Actuator
Type
Ab
Q
Cell
Phone
Actuator type determines the speed range and is factory set. Should the actuator Motor Speed Control PCB be replaced with
a spare, the actuator type must be set. Failure to set the correct type will invalidate the actuator performance specification
and warranty. To set the actuator types go to setting
[Ab]
in the secondary functions.