Using the
+
or
-
keys display the
required mask setting.
Auxiliary Input Mask OF
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
Press the
O
key to display
[PP]
.
This option is not used by the
DeviceNet DFU Module.
No Parity Bit
PRESS THE
KEY.
The displayed option will flash
indicating that it has been set.
53
DeviceNet Parity
AA
PF
DeviceNet Remote
Auxiliary Input (continued)
4. Stop/Maintain Control
When energised this will make the Aux input Open/Close control push-to-run.
When de-energised, the Aux input Open/Close control will be maintained. ESD is
always push to run (non maintained).
5. Remote I/P Setting
Ensure that the correct “Od” setting is selected
(refer to page 38)
.
For DeviceNet this is
[OP]
.
The factory default for
[PF]
is
[OF]
.
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD
and Stop/maintain is NC.
Aux I/P
4 3 2 1
Function
1 1 1 1
= F
Invert
0 0 1 1
= 3 i.e. set [PF] to [F3]
2. Open and close control is required along with 2 inverted digital signal inputs.
(Note that with this setting the open and close commands will be maintained.)
Aux I/P
4 3 2 1
Function
0 0 1 1
= 3
Invert
0 0 1 1
= 3 i.e. set [PF] to [33]
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input.
Aux I/P
4 3 2 1
Function
1 1 0 0
= C
Invert
1 0 0 0
= 8 i.e. set [PF] to [C8]