Setting instructions for actuators
including a CPT providing 4-20
mA analogue position feedback.
The CPT is an optional extra. It may be
internally or externally powered.
Check wiring diagram for inclusion and
connection details.
With
[HI]
Displayed, the (CPT)
20mA Output will Correspond to
Actuator Fully Open
If 20mA is required to correspond to
actuator closed use the
+
or
-
key to
change to
[LO]
.
PRESS THE
KEY.
The displayed option will flash
indicating that the option has been set.
NOTE:
If the actuator has options
Folomatic and CPT, redefining the CPT,
will require the Folomatic to be
recommissioned
(refer to Section 9.6
Folomatic
[OI]
page 35)
.
34
9.5
Option CPT [OI]
(Current Position Transmitter)