Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
81
Kinetix 7000 High Power Servo Drives
Technical Specifications - Kinetix 7000 High Power Servo Drives
Kinetix 7000 Drive Power Specifications
Attribute
2099-BM06-S
2099-BM07-S
2099-BM08-S
2099-BM09-S
2099-BM10-S
2099-BM11-S
2099-BM12-S
AC input voltage
342…528V AC rms three-phase (380…480V nom)
AC input frequency
47…63 Hz
Bandwidth
(1)
Velocity loop
Current loop
(1) Bandwidth values vary based on tuning parameters and mechanical components.
500 Hz
1300 Hz
500 Hz
500 Hz
PWM frequency
4 kHz
2 kHz
Main AC input current
Nom (rms)
Max inrush (A peak)
36.7 A
18.0 A
47.7 A
18.0 A
59.6 A
18.0 A
90.1 A
96.0 A
117 A
118 A
169 A
141 A
233 A
141 A
DC input voltage
450…750V DC
DC input current
42.9 A
55.7 A
69.7 A
105 A
137 A
204 A
281 A
Control power input Voltage
18…30V DC (24V DC, nom)
Control power DC input current
Nom (rms)
Maximum inrush (rms)
3.3 A
6.0 A
Continuous output current (rms)
40.0 A
52.0 A
65.0 A
96.0 A
125 A
180 A
248 A
Continuous output current (0-pk)
56.0 A
73.0 A
92.0 A
135 A
176 A
254 A
351 A
Peak output current (rms)
3 s duration
60 s duration
68.0 A
51.0 A
80.0 A
60.0 A
104 A
78.0A
154 A
115 A
163 A
138 A
312 A
234 A
372 A
273 A
Peak output current (0-pk)
3 s duration
60 s duration
96.0 A
72.0 A
113 A
84.8 A
147 A
110 A
217.7 A
162.6 A
230.5 A
195 A
441 A
331 A
526 A
386 A
Bus overvoltage
800V DC
Bus undervoltage
275…560V DC
(2)
(2) Bus undervoltage can vary based on input line voltage.
Continuous power output, nom
22 kW
30 kW
37 kW
56 kW
75 kW
112 kW
149 kW
Continuous power output (Hp)
30 Hp
40 Hp
50 Hp
75 Hp
100 Hp
150 Hp
200 Hp
Maximum power cycles/minute
AC line
DC bus
4 per minute (pre-charge provided by drive)
2 per minute (DC pre-charge provided by the regenerative power supply)
DC bus discharge time
3 minutes after removal of main AC power
Efficiency
97.5%
Total capacitance
(3)
(3) If DC input is supplied to 2099-BM09-S, 2099-BM10-S, or 2099-BM11-S drives, the precharge capability must be provided at the system level. Disconnect switches must not be used between the input
of the drive and a common DC bus without the use of an external precharge device.
1800
F
2400
F
3000
F
4500
F
6000
F
8400
F
8400
F
Short-circuit current rating
200,000 A (rms) symmetrical