![Rockwell Automation Allen-Brandley Kinetix 2000 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/rockwell-automation/allen-brandley-kinetix-2000/allen-brandley-kinetix-2000_original-instructions-manual_1475832050.webp)
50
Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
Kinetix 300 and Kinetix 350 EtherNet/IP Servo Drives
Environmental Specifications - Kinetix 300 and Kinetix 350 Servo Drives
Certifications - Kinetix 300 and Kinetix 350 Servo Drives
Attribute
Operational Range
Storage Range (nonoperating)
Temperature, ambient
0…40
C (32…104
F)
-10…+70
C (14…158
F)
Relative humidity
5…95% noncondensing
5…95% noncondensing
Altitude
Derate by 1% per 300 m (1000 ft) above 1500 m (5000 ft)
3000 m (9842 ft) during transport
Vibration
5…2000 Hz @ 2.5 g peak, 0.015 mm (0.0006 in.) displacement, max
Shock
15 g, 11 ms half-sine pulse (3 pulses in each direction of 3 mutually perpendicular directions)
Agency Certification
(1)
(when product is marked)
for declarations of conformity, certificates, and other certification details.
Standards
cULus
(2)
(2) UL has not evaluated the Safe Torque Off option in these products.
UL Listed to U.S. and Canadian safety standards (UL 508 C File E59272).
Solid-state motor overload protection provides dynamic fold-back of motor current when 110% of the motor rating is reached with a
peak current limit based on the peak rating of the motor as investigated by UL to comply with UL 508C (UL File E59272).
CE
European Union 2004/108/EC EMC Directive compliant with IEC 61800-3:2004 + A1:2012: Adjustable Speed Electrical Power Drive
Systems - Part 3; EMC Product Standard including specific test methods.
European Union 2006/95/EC Low Voltage Directive compliant with:
• IEC 61800-5-1:2007 - Adjustable speed electrical power drive systems.
• IEC 50178:1997 - Electronic Equipment for use in Power Installations.
Functional Safety
TÜV certified for functional safety: up to Performance Level (PL) d, Category 3 according to ISO 13849; up to SIL CL2 according to
IEC 61508, IEC 61800-5-2, and IEC 62061 when used as described in the Kinetix 300 EtherNet/IP Indexing Servo Drives User Manual,
publication
and the Kinetix 350 Single-axis EtherNet/IP Servo Drives User Manual, publication
.
RCM
Australian Radiocommunications Act, compliant with:
• Radiocommunications Act: 1992
• Radiocommunications (Electromagnetic Compatibility) Standard: 2008
• Radiocommunications Labeling (Electromagnetic Compatibility) Notice: 2008
• AS/NZS CISPR 11: 2002 (Group 1, Class A)
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
• Registration number: KCC-REM-RAA-2097
ODVA
EtherNet/IP conformance tested (applies to Kinetix 350 servo drives).
Ecodesign
These products are out of scope of the regulation because they are not intended for use in combination with induction motors.