![Rockwell Automation Allen-Brandley Kinetix 2000 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/rockwell-automation/allen-brandley-kinetix-2000/allen-brandley-kinetix-2000_original-instructions-manual_1475832034.webp)
34
Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
Kinetix 6000 Multi-axis Servo Drives
Maximum Power Cable Length
Although motor power cables are available in standard lengths up to 90 m (295.3 ft) and the Kinetix 6000 power rail is available in sizes up to eight
axes, to meet CE requirements and improve system performance the combined motor power length for all axes on the same DC bus must not
exceed 160 m (525 ft) for 200V-class systems and 240 m (787 ft) for 400V-class systems.
Cable Lengths for Compatible Linear Actuators
Actuator Cat. No.
Absolute High-resolution
(5V) Encoder
m (ft)
Absolute High-resolution
(9V) Encoder
m (ft)
Incremental/TTL
(5V) Encoder
m (ft)
MPMA-A
xxxxx
or MPAS-A
xxxxx
-V (ballscrew)
30 (98.4)
MPMA-A
xxxxx
or MPAS-A
xxxxx
-A (direct drive)
30 (98.4)
MPMA-B
xxxxx
or MPAS-B
xxxxx
-V (ballscrew)
90 (295.3)
MPMA-B
xxxxx
or MPAS-B
xxxxx
-A (direct drive)
30 (98.4)
MPAR-A
xxxxx
-V/M
30 (98.4)
MPAR-B
xxxxx
-V/M
90 (295.3)
MPAI-A
xxxxx
M3
30 (98.4)
MPAI-B
xxxxx
M3
90 (295.3)
LDAT-S
xxxxxx-x
B
x
30 (98.4)
Cable Lengths for Compatible Linear Motors
Motor Cat. No.
Absolute High-resolution
(5V) Encoder
m (ft)
Incremental/TTL
(5V) Encoder
m (ft)
Kinetix LDC or LDL
30 (98.4)
30 (98.4)