Common Accessories
In this example, system 1 contains two (single-wide) Kinetix 6000 drives using the safe-off feature wired with two (double-wide) Kinetix 6000 drives
in system 2. System 2 also includes the 2090-SEPM-B24-S IPIM module. The wiring headers with motion allowed jumpers have been replaced as
shown. The third axis in system 1 does not use the safe-off feature, so the wiring header and motion allowed jumper remain installed.
This multiple drive configuration also applies to the Kinetix 7000 drives. When wiring the Kinetix 7000 modules from drive-to-drive, use 1202-C10
cables.
Typical Multiple Drive Safe-off Configuration
IMPORTANT
Due to the current capacity limitation of the safe-off cable connectors, multiple safe-off drive configurations must not
exceed eight Kinetix 6000 or Kinetix 7000 drive modules.
1202-C02
1202-C10
1202-C03
1202-C03
1 2 3 4 5 6 7 8 9
Safe-off Control Circuit
Connections
Wiring Plug Headers with
Motion-allowed Jumper
2090-XNSM-M
Middle-drive Headers
2090-XNSM-T
Last-drive Header
2090-XNSM-W
First-drive Wiring Header
Kinetix 6000 Drives
System 1
Kinetix 6000 Drives
System 2
Drive-to-drive Safe-off Cables
2094-SEPM-B24-S
IPIM Module