Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives
Circuit Breaker/Fuse Specifications
The 2094-BC
xx
-M
xx
-M and 2094-BM
xx
-M drive modules use internal solid-state motor short-circuit protection and, when protected by suitable
branch circuit protection, are rated for use on a circuit capable of delivering up to 200,000 A.
Input Power Circuit Protection (LIM)
The 2094-BL02 line interface modules (LIM) contains supplementary protection devices and, when protected by suitable branch circuit protection,
is rated for use on a circuit capable of delivering up to 5000 A. When this module is used, protection on the line side of the LIM module is required.
Fuses must be class J or CC only.
The 2094-BL
xx
S and 2094-XL75S-C
x
LIM modules contain branch circuit rated devices suitable for use on a circuit capable of delivering up to
65,000 A (400V-class). Refer to the Line Interface Module Installation Instructions, publication
, for power specifications and more
information on using the LIM module.
Input Power Circuit Protection (without LIM)
The fuses and Allen-Bradley circuit breakers listed on
are recommended for use with 2094-BC
xx
-M
xx
-M IAM power modules when the line
interface module (LIM) is not used.
Control and DC-bus Circuit-protection Specifications
IAM Power Module
Cat. No.
Control Input Power
DC-bus Power
Bussmann Fuse
(1)
(1) Use FNQ-R-7.5 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A.
Allen-Bradley Circuit Breaker
(2)
(non-UL)
(2) Use 1492-SPM1D150 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A.
Bussmann Fuse
Mersen Fuse
(3)
(3) Mersen fuses were formerly known as Ferraz Shawmut.
2094-BC01-MP5-M
FNQ-R-10 (10 A) or
FNQ-R-7.5 (7.5 A)
1492-SPM2D060 or
1492-SPM1D150
FWJ-20A14F
DCT20-2
2094-BC01-M01-M
2094-BC02-M02-M
FWJ-40A
A70QS40-4
2094-BC04-M03-M
FWJ-70A
A70QS70-4
2094-BC07-M05-M
FWJ-125A
A70QS125-4
IMPORTANT
LIM modules (catalog numbers 2094-BL
xx
S and 2094-XL75S-C
x
) can provide branch circuit protection to the IAM power
module. Follow all applicable NEC and local codes.
Input Power UL Circuit-protection Specifications
Kinetix 6200 and Kinetix 6500 Drives
UL Applications
IAM Power Module
Cat. No.
Drive Voltage
(three-phase) nom
Bussmann Fuses
Cat. No.
Miniature CB
Cat. No.
Motor Protection CB,
(1)
Self-protected CMC
Cat. No.
(1) These Bulletin 140M Motor Protection Circuit Breakers, when used as self-protected (Type E) devices, and Bulletin 1489 circuit breakers can be used on only WYE power systems (480Y/277V).
Molded Case CB
Cat. No.
2094-BC01-MP5-M
360…480V
KTK-R-20 (20 A) Class CC
1489-M3D300
140M-F8E-C32
–
2094-BC01-M01-M
360…480V
KTK-R-20 (20 A) Class CC
140M-F8E-C32
2094-BC02-M02-M
360…480V
KTK-R-30 (30 A) Class CC
–
140M-F8E-C45
2094-BC04-M03-M
360…480V
LPJ-45SP (45 A) Class J
–
140G-G6C3-C50
2094-BC07-M05-M
360…480V
LPJ-80SP (80 A) Class J
140G-G6C3-C90