32
Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
Kinetix 6000 Multi-axis Servo Drives
Input Transformer for Control Power
Power Dissipation Specifications
Use this table to size an enclosure and calculate required ventilation for your Kinetix 6000 drive system.
Power dissipation specifications are based on these calculations. This is an example:
2094-BC02-M02-S with 4.52 A
DC
(=20%) converter DC current and 10.3 A
rms
(=100%) inverter output current.
Converter loss (36 W) + Inverter loss (142 W) = 178 W total power dissipation.
Attribute
Value
Cat. No.
(1)
(1) Variables (
xx-x
) determine the input voltage and wiring configuration.
Input volt-amperes
750VA
1497B-A10-
xx-x
-N
1000VA
1497B-A11-
xx-x
-N
1500VA
1497B-A12-
xx-x
-N
Input voltage
460V AC
Output voltage
120…240V AC
Bulletin 2094 Drive Modules
Usage as % of Rated Power Output (watts)
20%
40%
60%
80%
100%
IAM (converter) module
(1)
(1) Internal shunt power is not included in the calculations and must be added based on utilization.
2094-AC05-MP5-S
8
11
15
19
24
2094-AC05-M01-S
9
12
16
20
25
2094-AC09-M02-S
14
20
28
36
46
2094-AC16-M03-S
19
30
43
58
74
2094-AC32-M05-S
41
68
100
136
176
2094-BC01-MP5-S
18
21
25
29
34
2094-BC01-M01-S
33
2094-BC02-M02-S
36
44
54
64
75
2094-BC04-M03-S
50
67
87
110
135
2094-BC07-M05-S
71
101
137
179
226
IAM (inverter) module or AM module
2094-AC05-MP5-S or 2094-AMP5-S
28
32
37
41
46
2094-AC05-M01-S or 2094-AM01-S
31
38
46
54
62
2094-AC09-M02-S or 2094-AM02-S
34
45
57
70
84
2094-AC16-M03-S or 2094-AM03-S
48
68
91
116
144
2094-AC32-M05-S or 2094-AM05-S
104
156
212
274
342
2094-BC01-MP5-S or 2094-BMP5-S
46
54
61
69
77
2094-BC01-M01-S or 2094-BM01-S
57
73
90
108
126
2094-BC02-M02-S or 2094-BM02-S
53
72
93
116
142
2094-BC04-M03-S or 2094-BM03-S
94
130
169
211
255
2094-BC07-M05-S or 2094-BM05-S
121
183
252
326
407
Shunt module - 2094-BSP2
68
121
174
227
280