Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
Kinetix 2000 Multi-axis Servo Drives
These fuses and Allen-Bradley circuit breakers are recommended for use with 2093-AC
xx
-MP
x
IAM modules when the line interface (LIM) module is
not used.
Contactor Ratings
This table lists the recommended contactor ratings for IAM modules installed without a LIM module.
Transformer Specifications for Control Power Input
You can use any general purpose transformer with these ratings.
IMPORTANT
2094-AL
xx
S and 2094-XL75S-C2 line interface (LIM) modules can provide branch circuit protection to the IAM module.
Follow all applicable NEC and local codes.
Input Power Circuit-protection Specifications
Kinetix 2000 Drives
UL Applications
IEC (non-UL) Applications
Drive Cat. No.
Input Voltage/
Phase
Bussmann
Fuse
Miniature CB
Cat. No.
Motor Protection CB,
(1)
Self-protected CMC
Cat. No.
(1) These Bulletin 140M Motor Protection Circuit Breakers, when used as self-protected (Type E) devices, and Bulletin 1489 circuit breakers can be used on only WYE power systems (480Y/277V).
Miniature CB
Cat. No.
Motor Protection CB
Cat. No.
2093-AC05-MP1
170…264 AC
three-phase
(230V nom)
KTK-R-20 (20 A)
1489-M3D300
140M-F8E-C16
1489-M3D300
1492-SPM3D300
140M-F8E-C16
2093-AC05-MP2
2093-AC05-MP5
2093-AC05-MP1
170…264 AC
single-phase
(230V nom)
KTK-R-20 (20 A)
1489-M3D300
N/A
1489-M3D300
1492-SPM3D300
N/A
2093-AC05-MP2
2093-AC05-MP5
IAM Cat. No.
Input Voltage
Contactor
2093-AC05-MP1
170…264 AC
single-phase or three-phase operation
100-C23x10 (AC coil)
100-C23Zx10 (DC coil)
2093-AC05-MP2
2093-AC05-MP5
Attribute
Value
Input volt-amperes
500VA
Output voltage
200…240V AC