Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
61
Install the Module
Chapter 4
Emergency stop button
Door monitoring switch
No
Connect the devices between T0 and I0
and I1, noting that T0 is configured for
24V power supply.
3
Connect the devices between 24V DC
and I0 and I1.
Yes
Connect the device between I0 and T0,
and I1 and T1.
4
Light Curtain
Yes
Connect the OSSD1 and OSSD2 to I0 and
I1, respectively. Connect the 24V power
supply commons.
3 or 4 based on
light curtain
being used
Connected Device
Test Pulse from
Test Output
Connection
Schematic Diagram
Safety
Category
I0
I1
T0
T1
I0
I1
T0
T1
24V DC
I0
I1
T0
T1
OSS
D2
OSS
D1
I0
I1
T0
T1
In -
24V
DC
Com
OSSD2
OSSD1
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......