144
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8
Replacing POINT Guard I/O Modules
7.
Click
to the right of the safety network number to open the Safety
Network Number dialog box.
8.
Click Set.
9.
Verify that the Network Status (NS) status indicator is alternating red/
green on the correct module before clicking Yes on the confirmation dialog
box to set the SNN and accept the replacement module.
10.
Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
Scenario 3 - Replacement Module SNN Is Different from Original and No Safety Signature Exists
1.
Remove the old I/O module and install the new module.
2.
Right-click your POINT Guard I/O module and choose Properties.
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......