48
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 3
Guidelines for Placing Power Supplies and Modules in a System
Placing Series A Digital and
Analog Modules
Always install modules in accordance with their specified operating temperature
ratings, as listed in
, and provide a minimum of 5.08 cm (2 in.)
clearance above the modules.
•
Limit ambient temperature operation to 40 °C (104°F) if Series A POINT
Guard I/O modules are used without 1734-CTM spacer modules.
Figure 21 - Placing Series A Digital Modules for up to 40 °C (104 °F) Operation
•
In any system where you have any Series A POINT Guard I/O modules,
use a 1734-CTM spacer between every POINT Guard I/O module with
ambient operation between 40 °C (104 °F) and 55 °C (131 °F).
Insert a 1734-CTM module next to each standard I/O module (gray) if
that module’s thermal dissipation specification is more than 1 W.
Figure 22 - Placing Series A Digital and Analog Modules for Operation from
40 °C (104 °F)…55°C (131°F) max.
•
When using Series A POINT Guard I/O modules in your system limit the
power supply to 24V DC maximum, to limit the Series A POINT
Guard I/O module’s thermal dissipation.
See
System Temperature Derating When a 1734-IE4S Module Is Used on
for more information.
Placing Series B Digital
Modules
Always install modules in accordance with their specified operating temperature
ratings, as listed in
, and provide a minimum of 5.08 cm (2 in.)
clearance above the modules.
ATTENTION:
Vertical orientation requires careful attention to design details
and panel layout so that all modules in the stack must operate within their
rated operating temperature range.
For Vertical installations, be sure that 1734-CTM spacer modules are installed next
to any Series A POINT Guard IO modules operating above 40 °C ambient.
1734-
AENT
173
4-
IB8S/A
173
4-
IB8S/A
173
4-
OB8S/A
173
4-
IE4S/A
173
4-
IE4S/A
173
4-
IE4S/A
5.08 cm (2 in.)
1734-
AENT
173
4-
IB8S/A
173
4-
IB8S/A
173
4-
OB8S/A
173
4-
IE4S/A
173
4-
IE4S/A
173
4-
IE4S/A
1734-CTM
5.08 cm (2 in.)
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......