POINT Guard I/O Overview
Verify that the POINT Guard I/O firmware revision is correct prior to
commissioning the safety system. Firmware information for safety I/O modules
is available at
http://www.rockwellautomation.com/products/certification/safety
Verify that a safety administrator conducts a risk assessment on the machine and
determines module suitability before installation.
TIP
Field power must be applied to the 1734-IE4S module when updating
firmware.
ATTENTION:
Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in using the
system.
ATTENTION:
Use only appropriate components or devices complying with
relevant safety standards corresponding to the required safety category and
safety integrity level.
•
Conformity to requirements of the safety category and safety integrity level
must be determined for the entire system.
•
We recommend you consult a certification body regarding assessment of
conformity to the required safety integrity level or safety category.
You are responsible for confirming compliance with the applicable standards for
the entire system.
Table 1 - Requirements for Controlling Devices
Device
Requirement
Allen-Bradley Bulletin Safety Components
Emergency stop switches
Use approved devices with direct opening mechanisms complying with IEC/EN 60947-
5-1.
Bulletin 800F, 800T
Door interlocking switches,
limit switches
Use approved devices with direct opening mechanisms complying with IEC/EN 60947-
5-1 and capable of switching microloads of
24V DC, 3 mA.
Bulletin 440K, 440G, 440H for interlock switch
Bulletin 440P, 802T for limit switch
Safety sensors
Use approved devices complying with the relevant product standards, regulations, and
rules in the country where used.
Any Guardmaster product
Relays with forcibly- guided
contacts, contactors
Use approved devices with forcibly-guided contacts complying with EN 50205. For
feedback purposes, use devices with contacts capable of switching micro loads of
24V DC, 3 mA.
Bulletin 700S, 100S
Other devices
Evaluate whether devices used are appropriate to satisfy the requirements of safety
category levels.
-
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......