Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
107
Configure the Module for a SmartGuard Controller
Chapter 6
2.
Click Browse.
3.
Check ‘I want to input the address for the device on the selected network’.
4.
Browse to the DeviceNet network, being sure to
not
click OK when the
browse is complete.
If you are unable to browse the DeviceNet network and see the POINT
Guard modules, the modules may have been previously configured to an
incompatible data rate or node address. Attempt to add these modules on
an isolated network to determine the node address and data rate.
5.
Enter the current address for the device.
An out-of-box device uses address 63.
6.
Click OK
7.
Enter the new address for the device.
8.
Click Apply.
9.
Look for confirmation in the messages section.
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......