Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
17
POINT Guard I/O Overview
Chapter 1
Safety Precautions
Observe these precautions for proper use of POINT Guard I/O modules.
Installing and Replacing Modules
When cleaning modules, do
not
use the following:
•
Thinner
•
Benzene
•
Acetone
POINT Guard I/O Modules in
CIP Safety Systems
POINT Guard I/O modules are used in the POINT I/O platform and
implement CIP Safety protocol extensions over EtherNet/IP and DeviceNet
networks to communicate safety messages. POINT Guard I/O modules connect
to EtherNet/IP or DeviceNet networks via these network adapters.
ATTENTION:
As serious injury may occur due to loss of required safety function,
follow these safety precautions.
•
Never use test outputs as safety outputs. Test outputs are not safety outputs.
•
Do not use Ethernet, DeviceNet, or ControlNet standard I/O data or explicit
message data as safety data.
•
Do not use LED status indicators on the I/O modules for safety operations.
•
Do not connect loads beyond the rated value to the safety outputs.
•
Apply properly specified voltages to the module. Applying inappropriate
voltages may cause the module to fail to perform it’s specified function, which
could lead to loss of safety functions or damage to the module.
•
Wire the POINT Guard I/O modules properly following the wiring requirements
and guidelines in
•
Set unique network node addresses before connecting devices to the network.
•
Perform testing to confirm that device wiring, configuration, and operation is
correct before starting system operation.
•
Do not disassemble, repair, or modify the module. This may result in loss of
safety functions.
ATTENTION:
•
Clear previous configuration data before connecting devices to the network or
connecting input or output power to the device.
•
Configure the replacement device properly and confirm that it operates
correctly.
•
After installation of the module, a safety administrator must confirm the
installation and conduct trial operation and maintenance.
Table 2 - Network Adapters
Network
System
Adapter
(1)
(1) Not compatible with 1734-ADN, 1734-ADNX, 1734-APB, or 1734-ACNR adapters.
EtherNet/IP
GuardLogix
1734-AENT (firmware revision 3 or later)
1734-AENTR
DeviceNet
SmartGuard or GuardLogix
1734-PDN
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......