Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
121
Configure the Module for a SmartGuard Controller
Chapter 6
4.
To add a safety connection, from the Connection Name pull-down menu,
choose one of these options.
The more status that is read, the larger the packet size.
5.
From the Connection Type pull-down menu, for this example choose
Multicast.
6.
From the Configuration pull-down menu, for this example choose
Configuration signature must match.
7.
In the Requested Packet Interval (RPI) box, enter 10 ms.
8.
In the Connection Reaction Time Limit (CRTL), enter 40.1 ms.
Choose
Description
1734
-IB8S
[IN] Safety
Control of safety inputs
[IN]
Combined Status
(1)
- Muting
•
Control of safety inputs
•
Status for one bit for all inputs
•
Muting status is available
[IN] Pt. Status
•
Control of safety inputs
•
Individual status for each input point
[IN] Pt. Status -
Muting
•
Control of safety inputs
•
Individual status for each input point
•
Muting status available
[IN] Pt. Status-
Muting - Test Output
•
Control of safety inputs
•
Individual status for each input point
•
Muting status available
•
Test output status available
[OUT] Test
Control of test outputs
173
4-
OB
8S
[IN] Safety Monitor -
Combined Status - Power
•
Monitor safety outputs
•
Status for one bit for all outputs
•
Power status available
[IN] Safety Output Status
•
Individual status for each output point
[IN] Safety Output
Monitor
•
Individual status for each output point
•
Monitor safety outputs
[OUT] Safety
Control of safety outputs
17
34-I
E4S
(2
)
[IN] Channel and Combined
Alarm Status
Combined channel status and alarm status for each input point
[IN] Channel Status, Alarm
Status
•
Individual status for each input point
•
Combined alarm status for each input point
•
Power status
[OUT] Tach Reset
Resets a latched overfrequency condition and enables the module to
begin calculating frequency again.
(1) Most digital input connections use Combined Status.
(2) Other connection options are available via RSNetWorx for DeviceNet software, but their use with a SmartGuard controller
is not recommended.
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......