Appendix B
Table 16 - Fault Code Definitions for 1734-IE4S Modules
Fault Code
Description
Definition
Recommended Action
2
Signal Over Range
Exceeded configured range
Check field wiring and/or power
3
Signal Under Range
Below configured range
Check field wiring and/or power
4
Signal Test Failure
Undefined error for IE4S
If the problem persists, replace module
5
Dual Channel Discrepancy
Exceeded tolerance between dual channels
Check field sensors to determine cause of discrepancy
6
Error in other Dual Channel
Input
Partner channel faulted
Troubleshoot partner channel fault
100
Sensor Supply Overcurrent
Exceeded specification
Check field wiring and sensor power draw
101
Sensor Undercurrent
Too little current drawn from sensor power
Check field wiring and sensor power draw
102
ADC CPU Timing Fault
ADC missed a clock, failed a sync, or watchdog
(combination flag)
If the problem persists, replace module
103
3.3V Undervoltage
3.3V supply voltage was detected too low
If the problem persists, replace module
104
3.3V Overvoltage
3.3V supply voltage was detected too high
If the problem persists, replace module
105
CPU Fault
ADC failed register, instruction, or flag diagnostic
If the problem persists, replace module
106
Flash Fault
FLASH test detected bit errors
If the problem persists, replace module
107
RAM fault
RAM test detected bit errors
If the problem persists, replace module
108
Single Channel
Discrepancy
Dual measurements of single channel disagree
If the problem persists, replace module
109
Tach Dual Low
Both channels LO at same time
Check sensor signal timing
110
Undefined Error
Undefined error
If the problem persists, replace module
111
Flash Enable Fault
ADC's nonvolatile memory drawing too much current
(micro jumped to nonvolatile for some reason)
If the problem persists, replace module
112
Serial Pattern Fault
Serial communication pattern errors detected
Check field wiring for proper grounding/shielding
Verify that the temperature within the enclosure is not excessive
If the problem persists, replace module
113
Channel Uniqueness Fault
Pulse testing of ADC multiplexor revealed improper
channel
If the problem persists, replace module
114
Watchdog Fault
ADC watchdog timed out
If the problem persists, replace module
115
Sync Timeout Fault
ADC conversion out of sync
If the problem persists, replace module
116
Missing Clock fault
ADC detected a missing clock
If the problem persists, replace module
117
SCI Tx fault
Serial communication bit errors detected
Check field wiring for proper grounding/shielding
Verify temperature within enclosure is not excessive
If the problem persists, replace module
118
ADC fault
ADC test pattern failure
If the problem persists, replace module
119
ADC neighbor 1.8V fault
ADC detected out-of-range voltage on its partner
If the problem persists, replace module
120
ADC channel config
mismatch
Dual ADCs are not configured the same
If the problem persists, replace module
121
SPI sequence number
mismatch
Serial communication state machines are out of sync
If the problem persists, replace module
122
Runtime 3.3V over/under
error
3.3V supply voltage was detected too high or too low
If the problem persists, replace module
125
Field I/O power is missing
24V power is not within specification
Check field power supply and wiring
126
Startup 3.3V over/under
error
OV-UV detector failed startup test
If the problem persists, replace module
127
Sensor power/input wiring
error
Sensor power to input signal violation detected
Check field wiring
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......