112
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 6
Configure the Module for a SmartGuard Controller
4.
If you are pulse-testing the module, edit the parameters so that the
channels are pulse tested by Test sources 0 and 1, respectively.
5.
Double-click General to edit the Input Error Latch Time, if desired.
The default value is 1000 ms.
Safety Input Test Source
None
The test output that is used with the input.
None
Test Output 0
Test Output 1
Test Output 2
Test Output 3
Input Delay Time Off -> On
0…126 ms (in 6 ms increments)
Filter time for OFF to ON transition.
0 ms
Input Delay Time On -> Off
0…126 ms (in 6 ms increments)
Filter time for ON to OFF transition.
0 ms
Parameter Name
Value
Description
Default
Содержание Allen-Bradley 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Страница 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Страница 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Страница 22: ...22 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 1 POINT Guard I O Overview Notes ...
Страница 150: ...150 Rockwell Automation Publication 1734 UM013J EN P July 2014 Chapter 8 Replacing POINTGuard I O Modules Notes ...
Страница 180: ...180 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix C Specifications Notes ...
Страница 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Страница 190: ...190 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix E Configuration Parameters Notes ...
Страница 204: ...204 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix G History of Changes Notes ...
Страница 211: ......